The amperage a three-phase asynchronous electric motor draws is roughly set by its power and speed. On a 400 V supply a 4 kW model draws about 8 amps at rated load, a 7.5 kW around 14 amps and an 11 kW near 20 amps. The exact figure is on the motor plate; the reference tables below gather the real 400 V currents of DRG models by power and speed.
DRG Motor is a manufacturer, supplier and seller of electric motors. It is based in İzmir and ships quickly from there across all of Türkiye. To compare currents on real products, browse the online electric motor shop; to see every power step in one list, open the three-phase asynchronous electric motors category.
What sets the amperage: power, voltage and speed
Three things together fix a motor's rated current: shaft power (kW), the voltage it runs on (400 V here) and its speed. More power means more current — that is expected. Less obvious is speed: at the same kW, a low-speed (high-pole) model draws more amps than a fast one, because turning slowly to make the same power needs higher torque and therefore more current.
So "how many amps for this power?" has no single answer; you also have to state the speed. That is why the tables below are split in two: first current by power, then how the same power changes with speed.
Rated current by power: DRG reference table (1500 rpm)
In the most requested 4-pole (1500 rpm) class, here are the 400 V rated currents of common DRG aluminium models. The values come from each model's own plate data; every code links straight to its product page. For a quick pre-check, keep the motor current chart handy.
| Model | Power | Speed | Current (400 V) |
|---|---|---|---|
| DRG-112M-4-AL | 4 kW (5.5 HP) | 1500 rpm | 7.95 A |
| DRG-132S-4-AL | 5.5 kW (7.5 HP) | 1500 rpm | 10.7 A |
| DRG-112M-4K-AL | 5.5 kW (7.5 HP) | 1500 rpm | 10.7 A |
| DRG-132M-4-AL | 7.5 kW (10 HP) | 1500 rpm | 14.3 A |
| DRG-160M-4-AL | 11 kW (15 HP) | 1500 rpm | 20.4 A |
| DRG-132M-4K-AL | 11 kW (15 HP) | 1500 rpm | 20.4 A |
Click to see current electric motor prices and order nowSEE PRICES →
Same power, different speed: how pole count changes the current
This is the point many buyers skip when ordering. In the table below the same four powers appear at three speeds (2-pole 3000 rpm, 4-pole 1500 rpm, 6-pole 1000 rpm), all from real DRG aluminium models at 400 V. Seeing the same 11 kW draw 19.6 A at 3000 rpm but 22 A at 1000 rpm explains at a glance why panel and cable choices should never be made without the speed.
| Power | 3000 rpm (2-pole) | 1500 rpm (4-pole) | 1000 rpm (6-pole) |
|---|---|---|---|
| 4 kW | 7.45 A | 7.95 A | 8.99 A |
| 5.5 kW | 10.1 A | 10.7 A | 12 A |
| 7.5 kW | 13.7 A | 14.3 A | 15.4 A |
| 11 kW | 19.6 A | 20.4 A | 22 A |
The gap looks small but it feeds straight into the thermal relay range and the cable size. If you picked a low-speed electric motor, reading the current one step higher saves trouble in the field.
Is the current the same on aluminium and cast iron frames?
A frequent question: "Does the amperage change if I take cast iron?" No. The frame material changes mechanical strength and weight; the electrical values — power, voltage and rated current — stay the same. The aluminium and cast-iron version of the same type and speed carry the same amps on the plate. Below we put the two frames side by side for 4 kW and 11 kW.
| Model | Power | Frame | Current (400 V) |
|---|---|---|---|
| DRG-112M-4-AL | 4 kW | Aluminium | 7.95 A |
| DRG-112M-4-GG | 4 kW | Cast iron | 7.95 A |
| DRG-160M-4-AL | 11 kW | Aluminium | 20.4 A |
| DRG-160M-4-GG | 11 kW | Cast iron | 20.4 A |
Powers not in the list: what does 0.37–160 kW draw?
DRG covers a wide range — 0.25–11 kW in aluminium and from 0.55 kW upward in cast iron. The tables above show the most asked mid powers; for a different rating a rough estimate helps. On 400 V three-phase the rated current is about 2 amps per kW (for example 15 kW ≈ 30 A, 30 kW ≈ 60 A). This is only a first guess; for the exact figure check the model's plate and the motor current chart.
Once you have fixed the power and speed, find the right model by power step in the shop, and use the electric motor calculator while you decide.
Choosing cable and thermal relay by current
Rated current is not just a number that satisfies curiosity; it is the first input that sets cable size and the thermal relay range. As cable length and drawn current grow, so does the cross-section. For pre-sizing, the motor cable size calculator helps; set the exact value according to the motor plate and panel documentation.
Before any connection or measurement, switch off the supply, verify it is de-energised and have the work done by a qualified electrician. The current drawn at start-up can be several times the rated current; that is why star-delta or soft starting comes up, but that value is separate from the rated current shown on the plate.
Frequently asked questions
How many amps does a 4 kW three-phase electric motor draw?
At 400 V a 4-pole (1500 rpm) 4 kW model draws about 7.95 A at rated load. The 2-pole version of the same power draws 7.45 A and the 6-pole 8.99 A — so the current changes with speed.
Why does a low-speed electric motor draw more amps?
Making the same power at a lower speed needs higher torque, and higher torque means more current. That is why a 1000 rpm model draws a little more than a 3000 rpm model of the same kW.
Is the current written differently for 380 V and 400 V?
In practice they are the same class. The grid once called 380 V moved to 400 V in the standard; DRG plate currents are stated for 400 V and the small difference does not change the current noticeably.
I cannot read the amps on the plate — can you still find the right model?
Usually yes. Send the legible power, speed and any current figure; we will confirm the suitable DRG model and its expected current together.
To see the current price of the electric motor at the power and speed you need, visit the shop.SEE PRICES
Send a photo of your current motor nameplate and we will find the suitable DRG model together.Send on WhatsApp
Electric Motors Related to This Topic — Models and Current Prices
Suitability is not decided by power alone: compare the speed, voltage, mounting, shaft and fixing dimensions of your machine with the product data; if unsure, send us the nameplate of your current motor.
4 kW Three-Phase Motor 1500 rpm – DRG-112M-4 Aluminium
- 4 kW · 1500 rpm (4 poles)
- Aluminium frame · IEC 112M
- Shaft: 28 × 60 mm
5.5 kW Three-Phase Motor 1500 rpm – DRG-132S-4 Aluminium
- 5.5 kW · 1500 rpm (4 poles)
- Aluminium frame · IEC 132S
- Shaft: 38 × 80 mm
5.5 kW Compact Three-Phase Motor 1500 rpm – DRG-112M-4K Aluminium
- 5.5 kW · 1500 rpm (4 poles)
- Aluminium frame · IEC 112M
- Shaft: 28 × 60 mm
7.5 kW Three-Phase Motor 1500 rpm – DRG-132M-4 Aluminium
- 7.5 kW · 1500 rpm (4 poles)
- Aluminium frame · IEC 132M
- Shaft: 38 × 80 mm
11 kW Three-Phase Motor 1500 rpm – DRG-160M-4 Aluminium
- 11 kW · 1500 rpm (4 poles)
- Aluminium frame · IEC 160M
- Shaft: 42 × 110 mm
11 kW Compact Three-Phase Motor 1500 rpm – DRG-132M-4K Aluminium
- 11 kW · 1500 rpm (4 poles)
- Aluminium frame · IEC 132M
- Shaft: 38 × 80 mm