What protection uses to tell a locked rotor from a normal start is not the size of the current but how long that high current keeps flowing. During a healthy start the high inrush current falls back toward the rated value within a few seconds as the motor speeds up; with a locked rotor the current stays stuck at that high level and never drops. The protective device reads exactly this current–time difference: it allows a brief surge, and it trips when the high current refuses to fall.
DRG Motor is a manufacturer, supplier and seller of electric motors. It is based in İzmir and ships quickly across all of Türkiye, that province included. Before choosing protection you first need the motor's power and speed; compare suitable three-phase models in the online electric motor shop and see them together in the three-phase asynchronous electric motors category.
Why do starting current and locked-rotor current look alike?
At the instant power is applied the rotor is not yet turning. In that moment the motor behaves like a load drawing heavy current from its windings, several times the rated value. When an external obstruction jams the rotor so it cannot turn, the picture is the same: the rotor is stationary, so the current sits at that same high starting level. This is why you cannot answer "is this a start or a stall?" by looking at the peak current alone. The first snapshot of both events is almost identical.
The real difference is in time
What separates them is what happens next. In a sound start the rotor accelerates, and as speed rises the current drops quickly toward the rated value. Depending on the load inertia this takes anywhere from an instant to a few seconds. With a locked rotor the speed never rises; the current hangs at its high starting value and the windings heat up more with every second. So a normal start means "high current, then a drop", while a locked rotor means "high current, no drop".
| Condition | Current | Duration | Protection response |
|---|---|---|---|
| Normal starting | Several times rated current | A few seconds, then drops | Allows it, no trip |
| Locked rotor | High too, similar level | Stays, does not drop | Trips quickly |
| Overload while running | Just above rated | Lasts for minutes | Trips with delay |
Click to see current electric motor prices and order nowSEE PRICES →
What exactly does the protection measure?
A classic thermal overload relay has an inverse-time characteristic that weighs current against time: the higher the current, the sooner it trips. It is chosen to ride through the brief starting current but to trip when that same current flows continuously. The figure that sets this tolerance is called the trip class; it is picked to be longer than the motor's normal start time and shorter than the time the winding can survive undamaged. In digital motor protection relays the device measures both the starting current and the start time, and by watching whether the current begins to fall it can tell whether the motor is actually accelerating. The point is not to recite a fixed setting but to get the logic right: class and setting are always chosen from the motor's nameplate and the device's documentation.
What is the allowed locked-rotor time?
Most motor nameplates or catalogues give a time showing how long the winding can survive with the rotor locked before it is damaged; this value can differ for a cold and a hot start. The protection's job is to open the circuit before that time runs out. The shorter the time, the faster the protection must act. Loosening the setting so the relay "won't nuisance trip" can leave the motor unprotected the moment it stalls.
What if the start time is longer than the locked-rotor time?
Some loads make this harder. A large fan, a centrifuge or a machine with a heavy flywheel reaches speed very slowly; the start can approach or even exceed the locked-rotor time the winding can bear. In that case protection that watches only current cannot separate "still accelerating" from "stuck", because in both the current stays high for a long time. The answer is to add information that sees whether the motor is really turning: a speed-sensing switch, or a relay that tracks the start against a time-and-current curve. That lets the protection tell "high current but rotor turning" from "high current and rotor stopped".
Why it matters more as power grows
As the motor grows, the starting current grows too, and the heat released during a stall builds up faster. On a small motor a few seconds of delay changes little, while on a larger frame the same delay can stress the winding. The DRG three-phase asynchronous models below, all at 1500 rpm but at different powers, give a useful range for thinking about how protection scales.
| Model | Power (kW) | Speed (rpm) | Frame |
|---|---|---|---|
| DRG-90L-4 | 1.5 | 1500 | Aluminium |
| DRG-112M-4 | 4 | 1500 | Aluminium |
| DRG-132S-4 | 5.5 | 1500 | Aluminium |
| DRG-132M-4 | 7.5 | 1500 | Aluminium |
| DRG-160M-4 | 11 | 1500 | Aluminium |
Each model's rated current is on its nameplate; protection is sized to that rated current, not to the starting current. When choosing, also keep in mind the motor's connection (star/delta) and the supply voltage.
Common mistakes
- Oversizing the thermal relay to the starting current so it "won't nuisance trip" — which effectively leaves the motor unprotected during a stall.
- Choosing too low a trip class and suffering needless trips on every normal start.
- Relying on current alone for heavy-start loads without adding speed sensing.
- Ignoring ambient temperature and heat build-up inside the panel.
This kind of work is never done live. Before working in the panel, cut the power, verify it is dead, and leave the setting and wiring to qualified electrical personnel. If you are unsure which class and setting fit, photograph the motor nameplate and ask us.
Send a photo of your current motor nameplate and we will find the suitable DRG model together.Send on WhatsApp
Pick the right power and speed for your motor, then size the protection to match it.SEE PRICES
Frequently asked questions
Are locked-rotor current and starting current the same?
They are very close in magnitude, because in both the rotor is not turning. The difference is not the size of the current but how long it lasts: in a start the current falls, with a locked rotor it does not.
Can a thermal relay detect a locked rotor on its own?
If the start time is shorter than the locked-rotor time the winding can bear, an inverse-time thermal relay is usually enough. For heavy loads with very long starts you need speed sensing or a relay that measures the start time.
Why does the thermal relay sometimes trip while the motor starts?
Usually the trip class is too low for the load's start time, or the setting does not match the motor nameplate. The right approach is to have qualified personnel check the setting against the motor's rated current and start time.
At which power does protection selection get harder?
As power and inertia rise, the start lasts longer and the protection margin narrows. On large frames and heavy-flywheel machines, bringing speed information into the decision makes the distinction easier.
Electric Motors Related to This Topic — Models and Current Prices
Suitability is not decided by power alone: compare the speed, voltage, mounting, shaft and fixing dimensions of your machine with the product data; if unsure, send us the nameplate of your current motor.
4 kW Three-Phase Motor 1500 rpm – DRG-112M-4 Aluminium
- 4 kW · 1500 rpm (4 poles)
- Aluminium frame · IEC 112M
- Shaft: 28 × 60 mm
5.5 kW Three-Phase Motor 1500 rpm – DRG-132S-4 Aluminium
- 5.5 kW · 1500 rpm (4 poles)
- Aluminium frame · IEC 132S
- Shaft: 38 × 80 mm
7.5 kW Three-Phase Motor 1500 rpm – DRG-132M-4 Aluminium
- 7.5 kW · 1500 rpm (4 poles)
- Aluminium frame · IEC 132M
- Shaft: 38 × 80 mm
11 kW Three-Phase Motor 1500 rpm – DRG-160M-4 Aluminium
- 11 kW · 1500 rpm (4 poles)
- Aluminium frame · IEC 160M
- Shaft: 42 × 110 mm
1.5 kW Three-Phase Motor 1500 rpm – DRG-90L-4 Aluminium
- 1.5 kW · 1500 rpm (4 poles)
- Aluminium frame · IEC 90L
- Shaft: 24 × 50 mm